In brief: a Buchholz relay, a pressure relief device and a temperature indicator do different jobs. The correct combination depends on the transformer’s oil-preservation system, cooling arrangement and approved protection scheme. A list of accessories alone does not define which event will raise an alarm or trip the transformer.
This guide helps buyers compare the protection scope in oil-immersed transformer quotations. It is not an installation, commissioning or protection-setting procedure. The diagrams are original functional explanations, not equipment photographs, dimensional drawings or approved wiring diagrams.
Start with the tank design, not an accessory checklist
Before asking for a Buchholz relay, confirm whether the transformer has a conservator or a hermetically sealed tank. A conventional Buchholz arrangement requires an appropriate oil connection to a conservator; the same arrangement cannot simply be specified for every sealed distribution transformer. See our sealed versus conservator transformer comparison for the design distinction.
Also identify the oil compartments covered by the quotation. Where an on-load tap-changer has a separate oil compartment, its protective arrangement must be addressed separately in the equipment design. Do not assume that one main-tank accessory monitors every compartment.
What does a Buchholz relay detect?
A conventional Buchholz relay is located in the oil pipe between the main tank and conservator. Depending on the selected construction, it responds to collected gas, loss of insulating liquid and/or excessive liquid flow toward the conservator. Its contacts provide signals to the protection and annunciation scheme; the relay does not itself open the power circuit.
Gas-related and flow-related signals are commonly assigned different actions. However, the actual alarm/trip assignment, contact arrangement and relay version must be stated in the approved project documents, not inferred from the word “Buchholz.” Reinhausen’s Buchholz product information describes the conservator application; its MSAFE manual distinguishes gas, liquid-loss and flow responses for that product family.
Buyer check: request the relay identification, the protected compartment and a signal schedule. A conservator shown in a general photograph is not enough to confirm the supplied relay or its contact functions.
Pressure relief device versus pressure relay
A pressure relief device (PRD) provides a mechanical release path when tank pressure reaches its specified operating condition. It is not a guarantee against every tank failure. Discharge direction, personnel exposure, containment and maintenance access belong in the manufacturer’s equipment arrangement. Operation indication and electrical contacts depend on the selected device and options.
A rapid-pressure-rise relay or electronic pressure monitor instead detects pressure behaviour and sends a signal. It is not a substitute for a pressure-release path. A pressure/vacuum gauge is also not automatically a protective relay merely because it displays tank pressure. Qualitrol’s LPRD description and 930 pressure monitor description illustrate these separate functions.

Buyer check: ask which device is supplied, whether operation contacts are included, and how the status appears at the local panel or remote system. Do not copy an opening pressure or relay setting from another transformer.
OTI and WTI: two different temperature indications
An oil temperature indicator (OTI) indicates the temperature at its oil-sensing location. A conventional winding temperature indicator (WTI) uses a thermal-image arrangement: oil temperature is combined with a load-current-derived heating contribution calibrated for the transformer. It does not directly measure the temperature of each winding conductor. Direct fibre-optic winding sensing is a different measurement approach.
The distinction matters when a specification simply asks for “winding temperature monitoring.” Confirm whether the requirement is for a conventional thermal image, a calculated electronic value or direct sensing, and what local/remote outputs are needed. The Reinhausen BETECH manual, section 4.4, explains the oil-temperature and conventional winding-temperature versions.

Temperature devices may support alarms, trips and cooling control, depending on the selected equipment. Their stages must be coordinated with the transformer design and site protection philosophy. There is no single set of alarm/trip temperatures suitable for every project. Read our temperature-rise guide and the ONAN/ONAF cooling explanation alongside the manufacturer’s guaranteed data.
Supporting accessories do not replace fault protection
Oil-level indication helps operators observe the relevant liquid level; alarm contacts are an additional, specified function. A breather supports the moisture-control arrangement of the applicable breathing system. Neither should be treated as a universal replacement for gas, pressure, thermal or electrical protection.
Electrical protection is another coordinated layer. Its scope is determined by the system study and project design, rather than by adding a mechanical accessory. Buyers should therefore compare the transformer’s accessory list with the protection-panel scope and the interface between them.
What to ask for in a transformer quotation
- Tank and liquid system: preservation arrangement, insulating liquid and separate compartments, where applicable.
- Device schedule: function, proposed type, included options and responsibility for each supplied item.
- Signal interface: alarm/trip/control allocation, contact type and rating, auxiliary supply requirements and remote outputs.
- Site suitability: ambient conditions, enclosure requirements, installation environment and safe inspection access.
- Approval documents: accessory arrangement, terminal/interface drawings, signal list and applicable inspection/test records.
These points are useful for both a 20/24 kV oil-immersed distribution transformer and a 110/115 kV power transformer, but the final accessory package need not be identical. Voltage class alone does not determine the complete protection scope.
Need a configuration review? Send your transformer requirement with the available voltage, capacity, frequency, destination and site conditions. If you already have an accessory list or protection specification, include it for comparison; drawings and attachments are optional at the initial enquiry stage. Settings and commissioning remain subject to project-specific engineering approval.
Technical references and scope
Prepared by Apex Electrics for procurement and specification discussions, November 2026. The manufacturer references above support the functional distinctions, not a claim that every cited device is included in every Apex quotation. Confirm the supplied configuration in the order documents. The illustrations are original explanatory schematics; no manufacturer photographs or drawings have been reproduced.