5 MVA Step-Up Transformer Replacement

5 MVA oil-immersed step-up transformer with an 11 kV winding and two 0.4 kV windings.

Open transformer terminal compartment in the workshop
Workshop photograph of the open terminal compartment
RegionNigeria
ApplicationEquipment Replacement
Equipment scope5 MVA oil-immersed step-up transformer with an 11 kV winding and two 0.4 kV windings.

When Apex Technologies received this replacement order for Nigeria, the purchase specification already defined how the new transformer would connect on the low-voltage side. The equipment was rated at 5 MVA, but the cable schedule was just as important to the replacement: the customer specified 32 incoming single-core cables, each with a conductor cross-section of 500 mm².

The low-voltage connection

The schedule called for eight parallel cables for phase A, eight for phase B, eight for phase C and eight for neutral N. For a replacement with a cable arrangement like this, the outline and connection drawings need to show where the cable groups enter, how they reach the terminals and how much working space is available for termination. A voltage match alone does not tell the buyer whether the new unit will fit the existing cable layout.

Transformer terminal housing and radiator banks in the workshop
Workshop view of the terminal housing and radiator banks.

What the Nigeria order specified

The order was for a copper-wound, oil-immersed step-up transformer with one 11 kV winding and two 0.4 kV low-voltage windings. The accessory scope included a Buchholz relay. The 5 MVA figure is the stated transformer rating; it is not a separate rating for either low-voltage winding.

  • Destination: Nigeria, for replacement of existing equipment.
  • Transformer rating: 5 MVA; 11 kV and two 0.4 kV windings.
  • Low-voltage cable requirement: 32 × 500 mm² single-core cables, eight each for A, B, C and N.
Side view of the fitted transformer radiator banks
Side view of the radiator banks.

From workshop to packing

The workshop photos show the transformer with its terminal compartments accessible and the radiator banks fitted. The packing photos show protective wrapping and the covered equipment inside an open-top container during loading preparation. They document the workshop and packing stages, not installation or commissioning in Nigeria.

Transformer under protective wrapping in the workshop
The transformer wrapped for packing.
Covered transformer inside an open-top container
The covered transformer in an open-top container during loading preparation.

What to send for a replacement quotation

Planning a similar replacement? Use the replacement transformer interface checklist to compare cable entries, terminal geometry and the installation envelope before quotation.

Start with the existing nameplate and a photo of the cable compartment. If available, add the winding voltages, cable entry direction, conductor size and number of parallel runs for each phase and neutral. These details help us identify which dimensions and terminal arrangements need to be checked before a replacement is quoted. Send your replacement transformer requirements.